4-86
Component Definition and Maintenance
7000L-UM302B-EN-P – June 2013
7000 ―C‖ Frame - Marine
Replacement Procedure for DC/DC Power Supply
(Refer to Figure 4.65)
1. With the drive energized, check that all output voltages are
present. (View 1)
2. De-energize the drive, isolate and lock out the control power, and
remove all wire connections from the unit. (View 1)
3. Remove quantity of (4) M6 (H.H.T.R.S.) that will allow the
DC/DC Power Supply Assembly to be removed from the Low
Voltage Panel. (View 1)
4. Remove quantity of (4) M4 (P.H.M.S.) and Nylon Shoulder
Washers from the back of the Mounting Plate. ( View 2)
5. Replace old DC/DC Power Supply with the new one.
NOTE: Make sure the Black Insulation is between the DC/DC
Power Supply and the Mounting Plate. Repeat Steps 4, 3, 2, 1
in this order to replace unit. (View 2)
6. Ensure the ground wire of P4 plug is connected to the ground by
M10 bolt
DC/DC Power Supply
(cont.)