Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual
Page 39

Drive Installation 2-9
7000 “C” Frame - Marine
7000L-UM302B-EN-P – June 2013
Install CPVC Piping Splices
Open doors of capacitor cabinet (Cabinet #5) next to DC Link Choke
cabinet (Cabinet #6). Refer to Figure 2.4.
Remove capacitor from position #3, if installed (not all
configurations have a capacitor in this location). It is not necessary
to remove capacitor from position # 2.
A T T E N T I O N
A T T E N T I O N
Capacitors weigh up to 100 kg (220 lbs). Use
two people to remove the unit from the
structure.
Capacitor
Position #1
Capacitor
Position #2
Capacitor
Position #3
CPVC Pipe
Splices
Figure 2.4 – Capacitor Cabinet
Remove CPVC pipe splices shipped in the capacitor cabinet. Install
and tighten the 4 CPVC unions with strap wrench (¼ to ½ turn past
hand tight). Ensure O-ring is seated inside male end of union. Refer
to Figures 2.5, 2.6, 2.7 and 2.8. Do not use CPVC primer or cement.