Setting up diagnostic trending (cont.) – Rockwell Automation 7000L PowerFlex 7000 Medium Voltage AC Drive C Frame - Marine User Manual
Page 308

4-132
Component Definition and Maintenance
7000L-UM302B-EN-P – June 2013
7000 ―C‖ Frame - Marine
9. Repeat above steps until you have assigned the desired
parameters to all the traces from Trace1 to Trace16.
10. Now press F9 [TRIGGER] key. The first letter in the second line
on the screen will toggle between C and S. The letter C stands
for Continuous and S stands for Single shot. Select S for single
shot.
11. Press F2 [CONDITION] key. The cursor will move to the ―=‖
equal sign. This defines the trigger condition. Press up or down
arrow keys to select + sign as the trigger condition for our
example.
12. Press F3 [DATA] key. The cursor moves to the data field. In our
example we will enter 8 and then press Enter key.
13. Press F4 [RATE] key. The cursor moves to the rate field. Here
we will enter 0, which is the fastest sample rate (1 msec/sample)
and then press Enter key.
Setting up Diagnostic
Trending (cont.)