Rockwell Automation 9904-PCIC ControlNet 9904-PCIC Communications Card I.I. User Manual
Page 14
 
14
ControlNet PCI Communication Interface Card
9904-IN002A-US-P - March 2000
Table B ControlNet status interpretation continued
A or
B
Cause:
Action:
off
•
channel 
disabled
•
program network for redundant
media, if required
steady green
•
normal 
operation
•
none
flashing green/off
•
temporary 
network errors
•
check media for broken cables, loose 
connectors, missing terminators, etc.
•
If condition persists, refer to ControlNet 
International specifications.
flashing red/off
•
media fault
•
check media for broken cables, loose 
connectors, missing terminators, etc.
•
If condition persists, refer to ControlNet 
International specifications.
•
no other nodes 
present on 
network
•
add other nodes to the network
flashing red/green
•
incorrect node 
address
•
change PCIC node address so that it is less than 
or equal to UMAX
1
•
stop and restart the PCIC driver
•
incorrect 
network 
configuration
•
reconfigure the ControlNet network so that 
UMAX
1
is greater than or equal to the PCIC node
address
1
UMAX is the highest node address on a ControlNet network that can transmit data.