ControlNet PCI Communication Interface Card

9904-IN002A-US-P - March 2000

Table B ControlNet status interpretation continued

A or

B

Cause:

Action:

off

channel
disabled

program network for redundant
media, if required

steady green

normal
operation

none

flashing green/off

temporary
network errors

check media for broken cables, loose
connectors, missing terminators, etc.

If condition persists, refer to ControlNet
International specifications.

flashing red/off

media fault

check media for broken cables, loose
connectors, missing terminators, etc.

If condition persists, refer to ControlNet
International specifications.

no other nodes
present on
network

add other nodes to the network

flashing red/green

incorrect node
address

change PCIC node address so that it is less than
or equal to UMAX

1

stop and restart the PCIC driver

incorrect
network
configuration

reconfigure the ControlNet network so that
UMAX

1

is greater than or equal to the PCIC node

address

1

UMAX is the highest node address on a ControlNet network that can transmit data.