Publication 1799-IN004F-EN-P - September 2008

The DeviceNet wire insulation colors are shown below.

Auxiliary Power Specifications

P1 1799-D16U16V and -D16U16VL I/O Connector

Pin

Signal

Pin

Signal

Pin

Signal

8

Common Return

25

Input 11

41

Input 10

9

Output 4

26

Input 9

42

Input 8

10

+24V dc-GRP 0

27

Input 14

43

Common In GRP 1

11

Output 5

28

Input 12

44

Input 13

12

Output 7

29

Output 6

45

Input 15

13

Output 0

30

Not Used

46

Not Used

14

Output 1

31

Not Used

47

Not Used

15

+24V dc-GRP 0

32

Not Used

48

Not Used

16

Output 2

33

Not Used

49

Not Used

17

Output 3

50

Not Used

P3 DeviceNet Connector

Pin

Insulation Colors

1

Black

2

Blue

3

Shield

4

White

5

Red

ATTENTION

To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O
must be powered from a source compliant with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

To comply with UL restrictions, this equipment and all connected I/O must be powered
from a source compliant with the following:

10...30V dc Class 2 Power Supply or a 10...30V dc UL Listed or Recognized Power
Supply with isolated outputs limited to 200VA in each ungrounded output line. This
equipment and its power source must be mounted in a suitable enclosure with
proper spacings maintained.