Configure the parameters – Rockwell Automation 1799-D16U16BL 16 Input/16 Output Discrete Embedded I/O User Manual

Page 16

Advertising
background image

16 16 Input/16 Output Digital Embedded I/O Boards

Publication 1799-IN004F-EN-P - September 2008

Refer to this table for the word and bit definitions for the 1799-D16U16V and

1799-D16U16VL boards.

Configure the Parameters

The 1799 I/O boards have eight parameters that are configurable through a
DeviceNet configuration tool such as RSNetWorx for DeviceNet software. The
DeviceNet configuration tools require an electronic data sheet (EDS) for the 1799
I/O boards to configure the module’s parameters. Find the EDS files at
http://www.odva.org.

Use the descriptions in this table to help you configure the parameters.

The DeviceLogix capable boards, 1799-D16U16BL and 1799-D16U16VL, have
additional parameters, which are described in the DeviceLogix User Manual,
publication ACIG-UM001, and in the Embedded I/O for DeviceNet Technical Data,
publication 1799-TD001.

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produced 0 I7

I6

I5

I4

I3

I2

I1

I0

Produced 1 I15

I14

I13

I12

I11

I10

I9

I8

Consumed 0 O7

O6

O5

O4

O3

O2

O1

O0

Consumed 1 O15

O14

O13

O12

O11

O10

O9

O8

Where: I = Input, O = Output

Parameter

Description

Baud Rate

Controls the board’s communication rate.

Auto-Baud

Enables the board to match the network’s communication
rate. When enabled, Baud Rate parameter is ignored.

Input Off-to-On Filter Time

Controls the amount of time the input must be in the on
state before the board reports the input as on.

Input On-to-Off Filter Time

Controls the amount of time the input must be in the off
state before the board reports the input as off.

Output Idle State

Controls the state of each output when the DeviceNet
master is in an idle state.

Output Fault State

Controls the state of each output when the board loses
communication with the DeviceNet master.

Output Idle Value

Controls the value that outputs will have when the output
idle state is set to use idle value.

Output Fault Value

Controls the value that outputs will have when the output
fault state is set to use fault value.