16 Input/16 Output Digital Embedded I/O Boards 15

Publication 1799-IN004F-EN-P - September 2008

Communicate With Your Board

This board exchanges I/O with the master on the DeviceNet network through a
cyclic, polled, or change-of-state connection.

The 1799-D16U16B and 1799-D16U16BL boards consume and produce I/O data as

follows.

The 1799-D16U16V and 1799-D16U16VL boards consumes and produces I/O data

as follows.

Cyclic — the board produces and consumes its I/O cyclically at the rate configured
by the master on the DeviceNet network.

Polled — the master initiates communication by sending its polled I/O message to
the board. The board consumes the message, updates any outputs, and produces a
response containing the input data.

Change-of-state — a production occurs when an input changes. A heartbeat
production occurs if no input condition change occurs within the expected packet
rate. This heartbeat production tells the master that the board is ready to
communicate. Consumption occurs when data changes and the master produces
new output data to the board.

Refer to this table for the word and bit definitions for the 1799-D16U16B and

1799-D16U16BL boards.

I/O Connection Type

Consumes

Produces

Cyclic

2 bytes

3 bytes

Polled

2 bytes

3 bytes

Change-of-state

2 bytes

3 bytes

I/O Connection Type

Consumes

Produces

Cyclic

2 bytes

2 bytes

Polled

2 bytes

2 bytes

Change-of-state

2 bytes

2 bytes

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produced 0 I7

I6

I5

I4

I3

I2

I1

I0

Produced 1 I15

I14

I13

I12

I11

I10

I9

I8

Produced 2

Reserved

OFLT 1

OFLT 0

Consumed 0 O7

O6

O5

O4

O3

O2

O1

O0

Consumed 1 O15

O14

O13

O12

O11

O10

O9

O8

Where: I = Input, O = Output, OFLT 0 = Output Fault on one or more outputs in GRP 0,

OFLT 1 = Output Fault on one or more outputs in GRP 1