Publication 1799-IN004F-EN-P - September 2008

Attribute

Value

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on signal ports

±2 kV at 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5:

±500V line-line (DM) and ±1 kV line-earth (CM) on dc power ports

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

±2 kV line-earth (CM) on communication ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz

Certifications

Certification (when

product is marked)

(1)

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other certification

details.

Value

c-UR-us

UL Recognized Component Industrial Control Equipment, certified for US and
Canada. See UL File E65584.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

ODVA

ODVA conformance tested to DeviceNet specifications