Control Drawing for Class 1 Division 2 Applications
Hazardous Location
Class 1 Division 2, 
Groups A, B, C, and D
Non-Hazardous Location
Micro800 
Controller
USB Port
J3
V
max
= 5V DC
I
max
= 500
μA
L
i
= 1
μH
C
i
= 120 pF
Any associated apparatus with 
Universal Serial Bus (USB) connection
USB Port
V
oc
, I
sc
, L
a
and C
a
to be determined per
Capacitance and Inductance Values 
table
Capacitance and Inductance Values
Nonincendive
Equipment
Associated Apparatus
V
max
(or U
i
)
≥ V
oc
or V
t
(or U
o
)
I
max
(or L
i
)
≥ I
sc
or I
t
(or I
o
)
C
i
+ C
cable
≤ C
a
(or C
o
)
L
i
+ L
cable
≤ L
a
(or L
o
)
Capacitance and Inductance of the field wiring from the nonincendive equipment to the 
associated apparatus shall be calculated and must be included in the system 
calculations as shown in the table above.
Where the cable capacitance and inductance per foot are not known, the following 
values shall be used: C
cable
= 60 pF/ft, L
cable
= 0.2
μH/ft.
Wiring method must be in accordance with ANSI/NFPA70.