Publication 2080-IN003B-EN-P - April 2014

Current, per common,
max

5 A

N.A.

Turn on time/
Turn off time, max

10 ms

2.5

μs

ON: 0.1 ms
OFF: 1 ms

(1)

Applies for general purpose operation only. Does not apply for high-speed operation.

Relay Contacts Ratings

Maximum Volts

Amperes

Amperes
Continuous

Volt-Amperes

Make

Break

Make

Break

120V AC

15 A

1.5 A

2.0 A

1800V A

180V A

240V AC

7.5 A

0.75 A

24V DC

1.0 A

1.0 A

28V A

125V DC

0.22 A

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)

Temperature,
surrounding air, max

65 °C (149 °F)

Temperature,
non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g

Output Specifications

Attribute

Relay Output
(2080-LC30-16AWB,
2080-LC30-16QWB
only)

High Speed Output
(2080-LC30-16QVB
only)
(Outputs 0...1)

Standard Output
(2080-LC30-16QV
B only)
(Outputs 2....5)