8 Micro830 16 Point Programmable Controllers

Publication 2080-IN003B-EN-P - April 2014

Status Indicators

Mount the Module

Most applications require installation in an industrial enclosure to reduce the effects of electrical
interference and environmental exposure. Locate your controller as far as possible from power
lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and
AC motor drives. For more information on proper grounding guidelines, see the Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Mounting Dimensions and DIN Rail Mounting

Module Spacing

Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow
50.8 mm (2 in.) of space on all sides for adequate ventilation, as shown. An exception to this
spacing guideline is allowed for the side at which you are connecting the optional power supply,
2080-PS120-240VAC.

Input status

Run status

Force status

Power status

Fault status

Output status

Serial communications

status

45031

45032

Mounting dimensions do not include mounting feet or DIN rail latches.

100 mm (3.94 in.)

80 mm (3.15 in.)

90 mm (3.54 in.)