Rockwell Automation FactoryTalk Historian Classic for Batch User Guide User Manual

Page 46

Advertising
background image

Chapter 3 Collecting Batch Data

linked to a given batch. Only one deviation is created per parameter
or report, for the most severe limit violation. For example, if a
parameter has a verification method of HH/LL and the value
exceeds both the high and high-high limits, only one deviation event,
will be created for the high-high limit.

Column

Datatype Description

Example

uniqueid

text

Unique (create) ID

31

area

text

Area

THE_PAINT_COMPANY

starttime

date/time

Time stamp

2002-03-01 12:21:17.000

batchid

text

Batch ID

BATCH_ID-030102-3

EU

text

Engineering units

Gallons

unit

text

Unit name

REACTOR_1

phase

text

equipment module name

PHASE11

event

text

Batch event from the event
journal: Recipe Parameter
Deviation or Report

Parameter Deviation

Recipe Parameter Deviation

descript

text

Name of the parameter or
report that has exceeded

limits.

REPORT_10

esignatureid

integer

Unique electronic signature
number.

1

deviatedvalue

text

Actual value of the

parameter deviation.

101

targetvalue

text

Value of the target
parameter. The target

parameter is the recipe
parameter used in

calculating the limit when
the calculation method is

Percent or Relative.

100

limitviolated

text

Level of limit that was
violated: High/Low,
High-High/Low-Low, or

High-High-High/Low-Low-L
ow.

High/Low

limitvalue

text

Value of the limit that was
violated.

10

46

Rockwell Automation Publication BHIST-UM011A-EN-E-June 2014

Advertising