Mount the Capacitor Module

Clearance requirements for the Kinetix 5500 capacitor module are identical to the drive
modules. Refer to the Kinetix 5500 Servo Drives User Manual, publication

2198-UM001

, for

additional mounting information.

You can mount the capacitor modules to the right of any frame size, but are always rightmost in
any drive configuration.

Figure 2 - Kinetix 5500 Drive System Example with Capacitor Module

Table 1 - Capacitor Module Support

The recommended mounting hardware is M4 (#8-32) steel bolts. Apply 2.0 N•m (17.7 lb•in)
maximum torque to each fastener.

IMPORTANT

Mount drives in descending order, left to right, according to frame size with capacitor
modules always mounted on the far right.

The shared-bus connection system is required for capacitor module installations.

Drive Cat. No.

Fram

e S

ize

Standalone

Si

ngle Phase

Ope

ra

ti

on

Three-phase Operation

Standalone

Shared DC

Shared AC/DC

Shared AC/DC
Hybrid

Number of capacitor modules connected, max

2198-H003-ERS

(1)

(1) Catalog number 2198-H003-ERS and any drive in standalone single-phase operation is not compatible with the Kinetix 5500

capacitor module.

1

0

0

2198-H008-ERS

(1)

1

2

2198-H015-ERS

(1)

2

4

2198-H025-ERS

N/A

3

2198-H040-ERS

2198-H070-ERS

3

4

2198-H

xxx-ERS Drive System

(front view)

Frame 2 Drives

Frame 1 Drives

2198-CAPMOD-1300 Capacitor Module
(optional component)

Shared-bus Connection System
for DC Bus and 24V Control Power

Frame 3 Drive