Specifications – Rockwell Automation T7446L_H ICS Regent+Plus Relay Output Modules User Manual
Page 16
 
Relay Output Modules (T7446L, H)
 
1 6  
Industrial Control Services
Specifications
Safetybus Power
1.0 load units
Number of Outputs
Eight isolated circuits (four 
Form-C contacts, four 
selectable N.O. or N.C. 
contacts) 
T7446L
T7446H
Voltage Range
0.1 to 125 VAC/DC
5 to 250 VAC
5 to 125 VDC
Load Current
2.0 amps
2.0 amps
Minimum Load
0.1 VDC/10
m
A
5 VDC/10 mA
Surge Current
20 amps, 16 msec
20 amps, 16 msec
Over Voltage 
Protection 
750 VAC, 1 minute
1000 VAC, 1 
minute 
Rated Load 
 
resistive
 
110 VAC, 0.3 amps 
24 VDC, 1 amp 
 
250 VAC, 2 amps 
50 VDC, 2 amps 
inductive
110 VAC, 0.2 amps 
24 VDC, 0.3 amp 
250 VAC, 2 amps 
30 VDC, 2 amps 
Maximum 
Switching 
 
resistive
 
 
60 VA, 30 W 
 
 
500 VA, 100 W 
inductive
20 VA, 10 W
500 VA, 60 W
Contact 
Resistance 
 
50 mOhms, initial 
 
30 mOhms, initial 
Breakdown 
Voltage 
Logic to field
Same channel
Chnl to chnl
 
 
1000 VAC 
750 VAC 
2500 VAC 
 
 
2000 VAC 
1000 VAC 
2500 VAC 
Turn-On Delay
5 msec
10 msec
Turn-Off Delay
2 msec
10 msec
Heat Dissipation 4.5 Watts, 15
BTUs/hour
4.5 Watts, 15 
BTUs/hour