Testing and diagnostics, Front panel indicators – Rockwell Automation T7446L_H ICS Regent+Plus Relay Output Modules User Manual
Page 3
 
(T7446L, H) Relay Output Modules
 
P D - 7 0 1 7 M a r - 0 6  
3
logically turned off, the relay coil is de-energized (closing the 
N.C. contact). 
The relay provides logic-to-field isolation between the 
module’s logic and field circuits — protecting the output 
module from field signal over voltages, transients, and other 
electrical disturbances. 
Both types of relay output module use UL 508 approved 
relays. 
Testing and Diagnostics
Each module’s voter circuits are periodically tested by the 
processor modules. Discrepant data are sent through one of 
three legs of the I/O Safetybus to determine whether the 
module’s voter is able to outvote the incorrect data. A failure 
to return the correct majority-voted result to the processors 
produces an I/O module error indication at the processor 
modules and a module fault indication at the I/O module. 
Each type of module has a unique identification code that is 
read by the controller. This code lets the controller know 
which type of module is installed in each I/O chassis slot and 
how to address that module and its points specifically. If a 
module is removed, or is replaced with a module of a different 
type, the processor modules will indicate an I/O module error. 
Loopback logic tests periodically write data to the module and 
then read it back to determine whether the module’s I/O bus 
interface logic is functioning correctly. 
Front Panel Indicators
The relay output module is shown in Figure 2. The front 
panel contains active and fault status indicators, a shutdown 
indicator, and output status indicators for each output circuit. 
Active and Fault Status Indicators
These green and red LEDs indicate the overall health of the 
module. During normal operation the green ACTIVE 
indicator flashes at the controller's scan rate. If a module 
fault is detected the red FAULT indicator turns on and the 
green indicator turns off.