(T7446L, H) Relay Output Modules


P D - 7 0 1 7 M a r - 0 6

7

Relay Operation

The relays used on the T7446L contain SPDT contacts. For
the Form-A or Form-B selectable outputs, a jumper in the
module is used to select Form-A (N.O.) or Form-B (N.C.)
action.

The relays used on the T7446H contain two SPST contacts
(one normally closed and one normally open). Jumpers within
the module are also used to select the relay form. On the
Form-C output, there is no guarantee for make-before-break
or break-before-make.

Output Form Selection

Two sets of jumper posts are used to select the output form for
the selectable relays. The jumper locations are shown in
Figure 4. The jumper post designations are shown in Table 1.

Only one jumper shunt can be installed for each relay. The
modules are shipped with the jumpers positioned for normally
open contact outputs.

Table 1. Jumper Designations.

Jumper

Form

Description

E110

NO1

Selects normally open for relay 1

E111

NC1

Selects normally closed for relay 1

E120

NO2

Selects normally open for relay 2

E121

NC2

Selects normally closed for relay 2

E170

NO7

Selects normally open for relay 7

E171

NC7

Selects normally closed for relay 7

E180

NO8

Selects normally open for relay 8

E181

NC8

Selects normally closed for relay 8