Relay operation, Output form selection – Rockwell Automation T7446L_H ICS Regent+Plus Relay Output Modules User Manual
Page 7
 
(T7446L, H) Relay Output Modules
 
P D - 7 0 1 7 M a r - 0 6  
7
Relay Operation
The relays used on the T7446L contain SPDT contacts. For 
the Form-A or Form-B selectable outputs, a jumper in the 
module is used to select Form-A (N.O.) or Form-B (N.C.) 
action. 
The relays used on the T7446H contain two SPST contacts 
(one normally closed and one normally open). Jumpers within 
the module are also used to select the relay form. On the 
Form-C output, there is no guarantee for make-before-break 
or break-before-make. 
Output Form Selection
Two sets of jumper posts are used to select the output form for 
the selectable relays. The jumper locations are shown in 
Figure 4. The jumper post designations are shown in Table 1. 
Only one jumper shunt can be installed for each relay. The 
modules are shipped with the jumpers positioned for normally 
open contact outputs. 
Table 1. Jumper Designations.
Jumper
Form
Description
E110
NO1
Selects normally open for relay 1
E111
NC1
Selects normally closed for relay 1
E120
NO2
Selects normally open for relay 2
E121
NC2
Selects normally closed for relay 2
E170
NO7
Selects normally open for relay 7
E171
NC7
Selects normally closed for relay 7
E180
NO8
Selects normally open for relay 8
E181
NC8
Selects normally closed for relay 8