Rockwell Automation T7446L_H ICS Regent+Plus Relay Output Modules User Manual
Page 17
 
(T7446L, H) Relay Output Modules
 
P D - 7 0 1 7 M a r - 0 6  
17
Fusing (internal)
One 3.5 A, slow blow per 
output 
Note: Internal fuses are for 
protection of the printed cir-
cuit board only. Each output 
should be individually fused 
outside the module with a 
fuse rated for the output 
load. 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity, 
non-condensing 
Vibration
10 to 55 Hz:
 
±0.15mm 
Shock
Operating:
 
15 g, ½ sine wave, 11 msec 
Electromagnetic 
Interference 
•
IEC 801 Part 2 - Electrostatic
Discharges
•
IEC 801 Part 3 - Radiated
Electromagnetic Fields
•
ANSI/IEEE C37.90 - Surge
Withstand Capability
 
Level 3: Contact discharge of 
6 kV 
Level 3: 10 V/M, 27 MHz - 
500 MHz 
1 kV damped 1 MHz sine 
wave 
Safety
Certified to DIN V VDE 
0801 (non-interfering) and 
designed to meet UL 508 and 
CSA 22.2, No. 142-M1981 
Dimensions 
 
Height:
Width:
Depth:
 
12.6" (320 mm) 
1.27" (32 mm) 
10.12" (257 mm) 
Weight
4.0 lbs (1.8 kg)