Digital inputs (powered) – Rockwell Automation T8842 Trusted Versatile FTA User Manual
Page 10
 
Trusted
TM
Versatile FTA T8842
Issue 8 Aug 12
PD-T8842
10
Digital Inputs (Powered)
Figure 4 shows a channel configured to accept digital input signals from the field from devices which 
require power from the loop, e.g. fire input devices. 
Figure 4 Digital Inputs (with power)
The configuration shown above enables powered digital input devices to be interfaced to the Trusted
TM
TMR Zone Interface module. The channel is configured by fitting a 315mA fuse in position A, which 
provides circuit protection. Power for the field loop is derived from the dual 24Vdc source via the 2A 
fuse in position D, which acts as a link. The 250R resistor (7W 1%) allows the field device status to be 
monitored via the resistor voltage drop. It also acts as a field current limiter (96mA at 24V). The 
voltage at the field side of the resistor is detected by the module and used to determine the 
healthy/alarm state from the field device. 
For inputs which directly short the input or apply a fixed voltage (e.g. zener diode line monitoring), to a 
Zone Interface or Valve Monitor module, a 1k 0.6W resistor is required in position A. This is because 
the module requires an impedance to allow internal testing. Note that this will change the voltages seen 
by the module. 