11

Digital Inputs (Line Monitored)

Figure 5 shows a channel configured to accept line monitored digital input signals.

Figure 5 Digital Inputs (Line Monitored without power)

The configuration shown above enables line monitored digital input devices to be interfaced to the
Trusted

TM

TMR Zone Interface module (or a TMR Digital Input module). The channel is configured by

fitting a 315mA fuse in position B, which provides circuit protection. Power for the field loop is derived
from the dual 24Vdc source. The input signal is returned via a 2A fuse in position A, which acts as a
link.

For inputs without line monitoring components or using zener diodes, to a Zone Interface or Valve
Monitor module, a 1K 0.6W resistor is required in position A. This is because the module requires an
impedance to allow internal testing. Note that this will change the voltages seen by the module.

Field
Power
TBFPn

0V

Channel 1

B

Precision Resistor

Signal

A

0V

Field
Terminals
TBn

Signal
TBGn

Power Resistor

C

D

F

E

Fuse Field Power

3

2

1

1

2

3

4

m

2

2A

315 mA