Analogue inputs (4-20mA)

Figure 7 below shows the configurations required to accept input signals from current sourcing
analogue field devices.

Figure 7 Current Sourcing Analogue Inputs

The (optional) field power for each channel configured for analogue inputs is derived from the dual
24Vdc supplies via a 315mA fuse fitted in fuse position B, which provides circuit protection.

Current sourcing analogue field devices may be interfaced to the VFTA by fitting a 2A fuse in fuse
position E, which acts as a link, and a 50mA fuse in fuse position A, for circuit protection. This enables
current detection through the 250R resistor (high precision 0.1%). The fuse in fuse position A limits the
signal current to 50mA.

Current sinking analogue field devices may only be interfaced to the VFTA using a current mirror
interface. This interface may also include I.S. protection, e.g. MTL5040.

Field
Power
TBFPn

0V

Channel 1

B

Precision Resistor

Signal

A

0V

Field
Terminals
TBn

Signal
TBGn

Power Resistor

C

D

F

E

Fuse Field Power

3

2

1

1

2

3

4

m

2

50 mA

2A

315 mA