Analogue inputs (4-20mA)
Figure 7 below shows the configurations required to accept input signals from current sourcing 
analogue field devices. 
Figure 7 Current Sourcing Analogue Inputs
The (optional) field power for each channel configured for analogue inputs is derived from the dual 
24Vdc supplies via a 315mA fuse fitted in fuse position B, which provides circuit protection. 
Current sourcing analogue field devices may be interfaced to the VFTA by fitting a 2A fuse in fuse 
position E, which acts as a link, and a 50mA fuse in fuse position A, for circuit protection. This enables 
current detection through the 250R resistor (high precision 0.1%). The fuse in fuse position A limits the 
signal current to 50mA. 
Current sinking analogue field devices may only be interfaced to the VFTA using a current mirror 
interface. This interface may also include I.S. protection, e.g. MTL5040. 