3. Application

3.1. Module Configuration

There is no configuration required to the physical output module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the output
module after applications are downloaded and during Active/Standby changeover.

The IEC1131 TOOLSET provides the main interface to configure the output module. Details of the
configuration tools and configuration sequence are provided in PD-8082B Trusted

TM

Toolset Suite.

There are three procedures necessary to configure the output module. These are:

1. Define the necessary I/O variables for the field output data and module status data using the

Dictionary Editor of the IEC1131 TOOLSET.

2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O

module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.

3. Using the Trusted

TM

System Configuration Manager, define custom LED indicator modes,

per-channel default or fail-safe states, and other module settings.

3.2. T8480 Complex Equipment Definition

The T8480 I/O Complex Equipment Definition includes 8 I/O boards, referenced numerically by Rack
number:

Rack I/O Board

Description

Data Type

Direction

No. of
Channels

OEM Parameters

-

-

-

1

AO

Field Output Status

Analogue

Out

40

2

STATE

Field Output State

Integer

In

40

3

AI

Output voltage

Integer

In

40

4

CI

Output current

Integer

In

40

5

LINE_FLT

Line Fault Status

Boolean

In

40

6

DISCREP

Channel Discrepancy

Integer

In

3

7

HKEEPING Housekeeping Registers

Integer

In

57

8

INFO

I/O Module Information

Integer

In

11

Table 3 Complex Equipment Definition

There are two OEM parameters included in the first rack (AO Board). These OEM parameters define
the primary module position; declaring the module’s chassis and slot location. There is no need to
define the secondary module position within the IEC1131 TOOLSET. Where systems may be required
to start-up with modules in the secondary position as the active module, e.g. primary module is not
installed when application is started, the secondary module’s position should be declared in the module
definition of the System Configuration Manager.