Rack 1: ao, Rack 2: state, Table 4 oem parameters – Rockwell Automation T8480 Trusted TMR Analogue Output Module - 40 Channel User Manual

Page 20: Table 5 rack 1: ao descriptions, Table 6 rack 1: output current descriptions, Table 7 rack 2: state descriptions, Trusted, Module t8480

Advertising
background image

Trusted

TM

Module T8480

Issue 13 Apr 10

PD-T8480

20

OEM Parameter Description

Notes

TICS_CHASSIS The number of the

Trusted

TM

Chassis where

the Primary I/O module is
installed

The Trusted

TM

Controller Chassis is 1, and

Trusted

TM

Expander Chassis are 2 to 15

TICS_SLOT

The slot number in the
chassis where the Primary
I/O module is installed

The I/O module slots in the Trusted

TM

Controller

chassis are numbered from 1 to 8. The I/O
Module slots in the Trusted

TM

Expander Chassis

are numbered from 1 to 12

Table 4 OEM Parameters

3.2.1. Rack 1: AO

This board provides the connection to the logical output control signal for each of the field outputs.

Channel

Description

1

Field output channel 1 command

2

Field output channel 2 command

40

Field output channel 40 command

Table 5 Rack 1: AO descriptions

The output command scaling is designed to be consistent with the T8431 Analogue Input module.
This relationship is described by the table below:

Command

Output Current

-1024

Off (Minimum leakage current flowing)

0

4 mA

4096

20 mA

Table 6 Rack 1: Output Current descriptions

3.2.2. Rack 2: State

This board provides the majority voted numerical output state. This indicates the operational status of
the output channel and associated field connection.

Channel

Description

1

Field output channel 1 state

2

Field output channel 2 state

40

Field output channel 40 state

Table 7 Rack 2: STATE descriptions