Module status leds, Table 17 module status leds, Trusted – Rockwell Automation T8480 Trusted TMR Analogue Output Module - 40 Channel User Manual

Page 27: Module t8480

Advertising
background image

Trusted

TM

Module T8480

Issue 13 Apr 10

PD-T8480

27

4.2. Module Status LEDs

There are six module status indicators on the module front panel: three Healthy, one Active, one
Standby, and one Educated. The Healthy indicators are controlled directly by each module slice. The
Active, Standby, and Educated indicators are controlled by the FPU. The FPU receives data from
each of the module slices. The FPU performs a 2-oo-3 vote on each data bit from the slices and sets
the indicators accordingly.

The module status indicator modes and their meanings are described as follows:

INDICATOR

STATE

DESCRIPTION

Healthy

Off

No power applied to the module.

Amber

Slice is in the start-up state (momentary after
installation or power-up)

Green

Slice is healthy.

Red – flashing

Fault present on the associated slice but the slice is
still operational.

Red (momentary)

On installation – power applied to the associated
slice.

Red

The associated slice is in the fatal state. A critical
fault has been detected and the slice disabled..

Active

Off

Module is not in the Active state.

Green

Module is in the Active (or Maintain) state.

Red – flashing

Module is in the shutdown state if the Standby LED is
off.

Red – flashing

Module is in the fatal state if the Standby LED is also
flashing.

Standby

Off

Module is not in the Standby state.

Green

Module is in the Standby state.

Red – flashing

Module is in the fatal state. The Active LED will also
be flashing red.

Educated

Off

Module is not educated.

Green

Module is educated.

Green – flashing

Module is recognised by the Processor but education
is not complete.

Amber - Flashing

Active/standby changeover in progress

Table 17 Module Status LEDs

Advertising