Rockwell Automation 20D PowerFlex 700S/700H Drives, Frames 10...14 NEMA/UL Type 12 Door and Roof Filters User Manual

Powerflex

Advertising
background image

Installation Instructions

PFLEX-IN018C-EN-P

PowerFlex

®

700S and 700H Drives, Frames 10…14, NEMA UL

Type 12 / IP54 Replacement Door and Roof Filters

What This Kit Contains

• Metallic door filters (quantity varies per drive)
• Fiber door filters (quantity varies per drive)
• Metallic roof assembly filters (quantity varies per drive)
• Fiber roof assembly filters (quantity varies per drive)

Tools That You Need

• Hexalobular screwdriver
• Adjustable wrench

ATTENTION: To avoid an electric shock hazard, verify that the voltage on
the bus capacitors has discharged before servicing the drive. Check the DC
bus voltage at the Power Terminal Block by measuring between the +DC &
-DC terminals, between the +DC terminal and the chassis, and between
the -DC terminal and the chassis. The voltage must be zero for all three
measurements.

ATTENTION: HOT surfaces can cause severe burns. Do not touch the
heatsink surface during operation of the drive. After disconnecting power
allow time for cooling.

ATTENTION: The sheet metal cover and mounting screws on the ASIC
Board located on the power structure are energized at (-) DC bus potential
high voltage. Risk of electrical shock, injury, or death exists if someone
comes in contact with the assembly.

ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive
parts and assemblies. Static control precautions are required when
installing, testing, servicing or repairing this assembly. Component
damage may result if ESD control procedures are not followed. If you are
not familiar with static control procedures, reference A-B publication
8000-4.5.2, “Guarding Against Electrostatic Damage” or any other
applicable ESD protection handbook.