background image

4

Rockwell Automation Publication PFLEX-IN018C-EN-P - February 2011

PowerFlex® 700S and 700H Drives, Frames 10…14, NEMA UL Type 12 / IP54 Replacement Door and Roof Filters

4. Insert the following new metallic filters into each of the door filter

brackets.

5. Secure the brackets (with new filters) to the outside of the enclosure door

with the existing screws.

Frame

Voltage
Class

Drive Rating

Filter
Type

Dimensions (W x H x D)

Quantity

10

All

All

Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

2

11

All

All

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

2

12

All

All

Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

4

13

400V

1150 A

Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

2

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

2

1300 A & 1450 A Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

4

600V

All

Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

2

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

2

14

400V

All

Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

4

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

4

600V

1500 A

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

6

1900 A & 2250 A Metallic

450 x 330 x 22 mm (17.7 x 13 x 0.87 in.)

4

Metallic

650 x 330 x 22 mm (25.6 x 13 x 0.87 in.)

4