PowerFlex® 700S and 700H Drives, Frames 10…14, NEMA UL Type 12 / IP54 Replacement Door and Roof Filters
9. Insert the following new fiber filters, with the air flow direction arrow
pointing in toward the drive enclosure, into each of the door filter brackets.
See the illustration below for details.
10. Slide the filter brackets (with new filters) onto the screws on the inside of
the enclosure door and tighten the screws.
Frame
Voltage
Class
Drive Rating
Filter
Type
Dimensions (W x H x D)
Quantity
10
All
All
Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
2
11
All
All
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
2
12
All
All
Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
4
13
400V
1150 A
Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
2
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
2
1300 A & 1450 A Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
4
600V
All
Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
2
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
2
14
400V
All
Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
4
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
4
600V
1500 A
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
6
1900 A & 2250 A Fiber
450 x 330 x 45 mm (17.7 x 13 x 1.8 in.)
4
Fiber
650 x 330 x 45 mm (25.6 x 13 x 1.8 in.)
4
IMPORTANT
Verify the air flow direction on the fiber filters. You must install the
new filters with the air flow arrows pointing in the proper direction.
Air flow direction
through door filter
Air flow direction within
the drive enclosure
Air flow direction arrow
pointing in toward drive
Air flow direction
through door filter
Air flow direction within
the drive enclosure