Required equipment and software versions, Configuring an i/o connection – Rockwell Automation WebPak 3000  ControlNet Communications Board I/O with ControlLogix Processor User Manual

Page 2

Advertising
background image

2

Using WebPak

3000 ControlNet

Communications Option Board I/O With a ControlLogix

Processor

You can also contact the Rockwell Automation technical support division for the product related to your
question:

Required Equipment and Software Versions

Table 2 lists the equipment and software versions required to set up communications between a ControlLogix
processor and a WebPak 3000 drive.

If the firmware in your ControlLogix equipment does not meet the above requirements, contact the Control and
Information Group technical support division (1-440-646-6800) to obtain a copy of the appropriate
ControlFlash upgrade kit.

Configuring an I/O Connection

Before configuring an I/O connection, you must:

Configure the WebPak 3000 drive network parameters (refer to chapter 3 in D2-3425-2), set the network
drop number appropriately, and set the control source to network.

Verify that you have used RSNetWorx for ControlNet to configure the network containing the ControlLogix
chassis and WebPak 3000 drive.

Use the following procedure to configure an I/O connection:

Step 1. After opening the RSLogix 5000 software, verify that you are off-line with the ControlLogix processor.

You can configure an I/O connection when starting a new project or after opening an existing project,
but I/O can only be configured off-line.

Division

Telephone

E-mail/Web Address

Rockwell Software
(RSLinx, RSNetWorx for ControlNet,
RSLogix 5000 software)

1-440-646-7800

http://www.software.rockwell.com/support/

Control and Information Group
(ControlLogix system, ControlNet
network)

1-440-646-6800

[email protected]

Table 2 – Required Equipment and Software Versions

Equipment Description

Part Number

Version

RSLinx software

9355-WABENE

Version 2.20 or later

RSNetWorx for ControlNet software

9357-CNETL3

Version 2.25 or later

RSLogix 5000 software

9324-RDL300ENE

Version 6.00 or later

ControlLogix processor

1756-L1

Firmware version 6.20
or later

ControlLogix ControlNet bridge (1756-CNB or
1756-CNBR)

1756-CNB or 1756-CNBR

Series A, V1.19
Series B, V2.27 or later
Series D, V5.22

FlexPak 3000/WebPak 3000 ControlNet Network
Communications board

915FK2101

Version 2.2 or later