RDD-Series Rotary Direct Drive Bearingless Motor Installation Instructions 7

Publication RDB-IN001A-EN-P — October 2009

Ground the Shielded Signal Wires within a Power Cable

Always ground the shield on any signal wires inside a power cable. Connecting this
shield to chassis ground reduces the potential for voltage inductance and EMI.

Follow these steps to ground the shield wire on a 2090-CPBM7DF-xxAFxx or
2090-XXNPMF-xxSxx power cable.

1. Loop the signal wire pair to the overall cable shield as shown in the

diagram.

• Cable 2090-CPBM7DF-xxAFxx (shown) contains one signal wire pair.

• Cable 2090-XXNPMF-xxSxx contains two signal wire pairs.

2. Clamp all signal wire shields and the overall power-cable shield in the

power cable (chassis) ground clamp on the drive.

Grounding of Signal Wire Shields in a Power Cable

SHOCK HAZARD

If any shield on a power cable is not grounded, high voltage can be present on that
shield.

Make sure there is a connection to ground for all shield wires inside a power cable, and
for the overall power cable shield.

Failure to observe safety precautions could result in personal injury or damage to
equipment.

Shielded Signal Wires (one pair shown) within Power
Cable

Overall Power Cable Shield

Signal Wire Shield Contacts Overall Power
Cable Shield

Factory Supplied

Field Modified

All power and signal wire shields must connect to
machine ground.