2.6. Mechanical upgrade
Remove the SC300E ICCBs and replace with the 3x Trusted
TM
8161 Bridge Modules.
The Bridge module requires minimum configuration, namely the setting of Unit ID jumpers 0
to 3 to define the chassis address to Trusted™. These are situated on the Triguard chassis
as shown here.
The four backplane jumpers represent the binary address bits 1, 2, 4 & 8 respectively. On the
first SC300E chassis (containing the SC300E Bridge Modules), remove jumper 1 to
represent a Trusted
TM
address '2'. On the subsequent SC300E chassis the jumpers must be
left as they are.
Connectors J1-3 on the TC-325-02 card, plug into the three 26-way diagnostic headers on
the SC300E backplane. The Hotlink cable from the Trusted
TM
Expander Interface adapter
plugs into 12-way J4.