Clicking on a SC300E chassis in the Trusted
TM
System Configuration tool and selecting
‘Jumper Config’ will display the required jumper settings for that chassis.
The link settings on the Triguard BIC chassis refer to the ‘Triguard Chassis Number’ not the 
‘Logical Chassis Number’ which is the overall position of the chassis in the Trusted
TM
system.
The Controller rear view shows all connections 
available via the Interface Adapters. 
The Processor Interface Adapter provides 
connection for system alarms and Modbus RTU 
ports on the TMR Processor, as well as 
enabling features such as Modbus master and 
IRIG-B time synchronisation. 
The Expander Interface Adapter has four or 
seven connections available to individual 
Trusted
TM
Expanders or the SC300E Main
Chassis using the Trusted
TM
SC300E Interface
Cable Assembly TC-322-02.
Other serial and Ethernet communications 
capability is accessed through the 
Communications Interface Adapters. Ethernet 
RJ45 connection is specifically required for Peer 
to Peer and OPC. 
Due to the low current requirements of the 5Vdc supply to the 8161 Bridge modules it may be 
necessary to fit a MXD dummy load module in the chassis, if no I/O modules are installed. 
This is to provide a minimum load for the chassis 5Vdc power supplies. 
Comms interface
adapter - DCS, peer
to peer & EWS
Expander
interface
adapter
Processor interface
adapter
(IRIG-b, MODBUS)
Connections to bus
adapter and Plantguard
Expanders
Interface cable
Comms interface
adapter - DCS, peer
to peer & EWS
Expander
interface
adapter
Processor interface
adapter
(IRIG-b, MODBUS)
Connections to bus
adapter and Plantguard
Expanders
Interface cable
Connections to bus
adapter and
Trusted
TM
Expanders