2 wiring – Rockwell Automation SA3000 High Power Modules User Manual

Page 26

Advertising
background image

3-2

High Power SA3000 AC Power Modules

3.2

Wiring

System wiring is to be done according to the supplied wiring diagrams (W/Es), which
are application-specific. Sections 3.2.1 through 3.2.3 provide additional information on
fuses and recommended wiring.

3.2.1 Fuses

Fuses are provided to protect the Power Module's DC bus, 115 VAC control power
input lines, and individual IGBT phase modules. See table 3.1 for the fuse values.

3.2.2 Wire Sizes

Input wiring should be sized according to applicable codes to handle the SA3000
Power Module's continuous-rated input current. Output wiring should be sized
according to applicable codes to handle the SA3000 Power Module's continuous-rated
output current. Recommended wire sizes are shown in table 3.2. Terminals should be
tightened to the torque values provided in table 3.3.

!

ATTENTION: The user is responsible for conforming with all applicable
local, national, and international codes. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.

!

ATTENTION: The NEC/CEC requires that upstream branch circuit
protection be provided to protect input power wiring. Install the fuses
recommended in table 3.1. Do not exceed the fuse ratings. Failure to
observe this precaution could result in damage to, or destruction of the
equipment.

Table 3.1 – Fuse Ratings

Fuse

Circuit

Fuse Current

Rating

Fuse Voltage

Rating

Rockwell

P/N

FPM A,B,C

DC Bus

1000 A

1000 VAC

64676-80P

F103 A,B,C
F104 A,B,C
F105 A,B,C

IGBT Phase

Modules

630 A

1000 VAC

64676-79AZ

1FU

115 VAC

5 A

600 VAC

64676-29R

3FU

115 VAC

3.2 A

600 VAC

64676-29P

Table 3.2 – Recommended DC Bus Input and AC Output Wire Sizes

SA3000 Output Rating

Size of Wire

1

1. NEC-recommended cable types: 40

o

C (104

o

F) copper wire.

534A

2 x 600 Kc Mil (304 mm

2

)

972A

3 x 600 Kc Mil (304 mm

2

)

1457A

4 x 1000 Kc Mil (507 mm

2

)