B.1 modifying internal dc bus voltage thresholds – Rockwell Automation SA3000 High Power Modules User Manual

Page 60

Advertising
background image

B-4

High Power SA3000 Power Modules

B.1 Modifying Internal DC Bus Voltage Thresholds

The programmer can use three different pre-defined tunable variables to specify three
bus voltage thresholds:

OVT_E0% overvoltage threshold

UVT_E0% undervoltage threshold

PLT_E0% power loss threshold

These thresholds define the boundaries for specific operating levels. Figure B.3 shows
the relative bus voltage operating ranges and how the tunable variables can affect
these ranges.

Important: The three tunable variables listed above should be tuned before enabling

the execution of the control algorithm in the PMI Processor to ensure that
internal DC bus voltage warning thresholds are set to levels appropriate
for the application. See instruction manual S-3042, SA3000 Drive
Configuration and Programming, for the acceptable value ranges.

Figure B.3 – Internal DC Bus Operating Range

0

1

2

Time in

Seconds

Internal DC
Bus Voltage

Power Loss Threshold
(Tunable PLT_E0%)

Undervoltage Minimum
(Tunable UVT_E0% minus
5% of nominal bus voltage)

Undervoltage Threshold
(Tunable UVT_E0%)

Nominal Bus Voltage

Overvoltage Threshold
(Tunable OVT_E0%)

Overvoltage Maximum
(Tunable OVT_E0% plus
5% of nominal bus voltage)

Hardware Overvoltage
(a preset value)

Normal Charging