Instruction Manual D2-3537

Step 9: Verifying the
Installation

Follow the normal steps for verifying drive installation and operation. Refer to the
drive Hardware Reference and Software Start-up manuals.

Performing Continuity Tests

In these tests you are verifying continuity, a short circuit, between the two test
points. The continuity mode on a digital multi-meter provides the easiest method
for performing this test. Place one meter lead on the first test point and the meter
should beep when you place the other lead on the second test point.

If your meter does not have a continuity mode, you can use a resistance mode.
Place one meter lead on the first test point and the meter should indicate a short
circuit (read approximately zero ohms) when you place the other lead on the
second test point.

Task

Description
Disconnect J4A from the PIC board on a LiquiFlo 1.0 drive or the PMC board on a LiquiFlo
1.5 drive
Confirm continuity between the points specified in

Table A

Reconnect J4A

Confirm continuity between the points specified in

Table B

A

B

C

C

J4/J4A/J4B

CAP (-) and

CAP MID

CAP (+)

Pin 1

Table A J4 Continuity Tests

Table B Capacitor Bank Continuity Tests

Test Points

(1)

Meter Reading

J4 End of Cable

Resistor
Assembly End of
Cable

(2)

J4:Pin 1

BUS (+)

Continuity or
approximately zero
ohms

J4:Pin 3

BUS MID

J4:Pin 5

BUS (-)

Test Points

(1)

(1)

If you are unfamiliar with continuity tests, refer to

Performing

Continuity Tests on page 10

.

Meter Reading

Capacitor Bank
End of Cable

Resistor
Assembly End of
Cable

(2)

(2)

See

Wiring Diagram for Reference on page 12

.

CAP (+)

BUS (+)

Continuity or
approximately zero
ohms

CAP MID

BUS MID

CAP (-)

BUS (-)

If you have a...

... refer to these publications:

LiquiFlo 1.0 drive

• D2-3410, LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive

Software Start-up

• D2-3411, LiquiFlo AC Power Modules Hardware Reference, Installation and

Troubleshooting

LiquiFlo 1.5 drive

• D2-3494, LiquiFlo 1.5 AC Power Modules Hardware Reference, Installation,

and Troubleshooting

• D2-3495, LiquiFlo 1.5 AC General Purpose (Volts/Hertz) and Vector Duty

Drive Software Start-Up and Reference Manual