3.6. Module – pi641 / pi741 (analogue output module)
DESCRIPTION
This definition will open a single PI641 or PI741.
OEM PARAMETERS
OEM parameter Valid numbers Description
CHASSIS
2-29
Logical chassis and slot number where the CIO_AO is located.
SLOT
1-15
PHYSICAL MODULE:
RACK 1: (AO)
4 INTEGER outputs
RACK 2: (DIAG)
2 INTEGER inputs
Word 1 Diagnostic bits
bit 0
Slice A
=1
slice is not responding or there is an error
=0
slice is responding
bit 1
Slice B
=1
slice is not responding or there is an error
=0
slice is responding
bit 2
Slice C
=1
slice is not responding or there is an error
=0
slice is responding
bit 3
Module offline or missing
=1
offline or missing
=0
online
bit 4
Single slot hot repair
=1
in progress
=0
not in progress
bit 5
Discrepancy errors
=1
faults detected
=0
no faults detected
Word 2 Slot number of active module
RACK 3: (FAULTS)
2 INTEGER inputs
Word 1 Discrepancy errors, channels 1-4 (bit 0 = channel 1)
Word 2 LFD errors, channels 1-4 (bit 0 = channel 1)