Trusted, Cs300 bridge module – Rockwell Automation CS300 Trusted Bridge Module User Manual
Page 22
 
Trusted
TM
CS300 Bridge Module
Issue 02 Feb 10
PD-8162
22
RACK 4: (CALIB) 
 
4 BOOLEAN outputs (one per channel) which determine if the AO output data is taken from
RACK 1 (AO) or from RACKs 5-7 (CALIB_x). 
 
=0, output data taken from RACK 1 (AO)
=1, output data taken from RACKs 5-7 (CALIB_x)
RACK 5: (CALIB_A) 
 
4 INTEGER outputs
Output data used for Slice A on the AO module. Only used if the corresponding Boolean output
in RACK 4 (CALIB) is TRUE. 
RACK 6: (CALIB_B) 
 
4 INTEGER outputs
Output data used for Slice B on the AO module. Only used if the corresponding boolean output
in RACK 4 (CALIB) is TRUE. 
RACK 7: (CALIB_C) 
 
4 INTEGER outputs
Output data used for Slice C on the AO module. Only used if the corresponding boolean output
in RACK 4 (CALIB) is TRUE. 
 
NOTES: 
Discrepancy errors will only be checked if the AO module has a configured AI monitor module. 
Discrepancy errors indicate a difference between the output value on an AO and the voted input value 
on the AI monitor. 
LFD errors will only be checked if the AO module has a configured AI monitor module and LFD testing 
is enabled on that AO module. 
The calibration racks (4-7) can be used to aid calibration of the D/A converters on the AO modules. 
They allow different values to be sent to each slice's D/A converter, allowing each to be calibrated 
individually.