3.9. Module – pi627 / pi727 / pi627_fs / pi727_fs (digital output module)
DESCRIPTION 
This definition will open a single PI627 or PI727. If the module is configured as 3-2-1 then the ‘_fs’ 
version is required and the option must also be marked in the system configuration for this module. 
 
OEM PARAMETERS 
OEM parameter Valid numbers Description 
CHASSIS 
2-29
Logical chassis and slot number where the CIO_DO is located.
SLOT
1-15
 
PHYSICAL MODULE: 
RACK 1: (DO) 
 
32 BOOLEAN outputs
RACK 2: (DIAG) 
 
2 INTEGER inputs
Word 1 Diagnostic bits
bit 0
Slice A
=1
slice is not responding or there is an error
=0
slice is responding
bit 1
Slice B
=1
slice is not responding or there is an error
=0
slice is responding
bit 2
Slice C
=1
slice is not responding or there is an error
=0
slice is responding
bit 3
Module offline or missing
=1
offline or missing
=0
online
bit 4
Single slot hot repair
=1
in progress
=0
not in progress
bit 5
Discrepancy errors
=1
faults detected
=0
no faults detected
bit 6
LFD faults
=1
faults detected
=0
no faults detected
Word 2 Slot number of active module