Original instructions – Rockwell Automation MSR42 Curtains Configuration and Diagnostic Software Tool User Manual User Manual

Page 38

Advertising
background image

36

Light Curtain Multi-Function Control Module User Manual

Original instructions

Following the download procedure according

chapter 5.5.1 on page 31 selecting the flag “Use Unit protection key” (Figure 44) the “Password dialog”

window is expanded (

Figure 52) and offers the following options:

• Set new unit protecting key

Set a key for an unprotected controller.
Enter the user download password, the protection key and confirm the key according the dialog window.

• Download with existing unit protection key

Download a configuration to a protected MSR42 controller.
Enter the user download password and the existing protection key.

• Change existing unit protection key

Download a configuration to a protected MSR42 controller and change the key.
Enter the user download password, the existing protection key, the new key and confirm the new key.

• Clear existing unit protection key

Download a configuration to a protected MSR42 controller and clear the key.
Enter the user download password and the existing protection key.

Figure 52: Password dialog for downloading and protecting a configuration

The download procedure continues according 5.5.1 step 7.

In case an invalid user password is used, the following message appears:

Store your Unit Protection Key safely and assure that only authorized personal have access to it.
Without the Unit Protection Key, a protected MSR42 controller may not be reconfigured. It has to be replaced
with a new control unit!