Light Curtain Multi-Function Control Module User Manual

Original instructions

Table 3 (* = a setting smaller or close to the total response time may influence the stability of the muting system)

Figure 65: Configuration window for “two sensor L-type”

A time t(sense) of 4 s is recommended in the standard IEC 62046

Figure 66 shows the corresponding wiring diagram of the MSR42 control unit configured with the “two sensor L-type” muting mode.

For this muting mode two mute disable inputs may be configured. If selected these signals must be “high” in order for a mute condition to take place
(See chapter 5.6.7 on page 39).

Parameter

Default Value

Max./Min. Values

Possible Settings

T(sens) [Figure 64]

2 s

Min.: 50 ms

Max.: 10 s

Min.: N x 0.05 s

T(mute) [Figure 64]

5 min

Min.: 0 ms

Max.: 10 days

(*)

T(msdel) [5.6.5]

50 ms

Min.: 0 ms

Max.: 2.55 s

N x 0.01 s

Muting lamp monitoring [5.6.2]

yes

yes/no

Mute dependant override [5.6.4]

yes

yes / no

T(mdo) [5.6.4]

5 s

Min.: 0 ms

Max.: 20 min

N x 5 s

Mute disable signal [5.6.7]

no

yes / no

Micro 400 interruption monitoring [5.6.8]

yes

yes

T(espe) [5.6.8]

2 s

Min.: 0 s

Max.: 10 s

N x 0.05 s (*)