Original instructions – Rockwell Automation MSR42 Curtains Configuration and Diagnostic Software Tool User Manual User Manual
Page 48

46
Light Curtain Multi-Function Control Module User Manual
Original instructions
Table 3 (* = a setting smaller or close to the total response time may influence the stability of the muting system)
Figure 65: Configuration window for “two sensor L-type”
A time t(sense) of 4 s is recommended in the standard IEC 62046
Figure 66 shows the corresponding wiring diagram of the MSR42 control unit configured with the “two sensor L-type” muting mode.
For this muting mode two mute disable inputs may be configured. If selected these signals must be “high” in order for a mute condition to take place
(See chapter 5.6.7 on page 39).
Parameter
Default Value
Max./Min. Values
Possible Settings
T(sens) [Figure 64]
2 s
Min.: 50 ms
Max.: 10 s
Min.: N x 0.05 s
T(mute) [Figure 64]
5 min
Min.: 0 ms
Max.: 10 days
(*)
T(msdel) [5.6.5]
50 ms
Min.: 0 ms
Max.: 2.55 s
N x 0.01 s
Muting lamp monitoring [5.6.2]
yes
yes/no
Mute dependant override [5.6.4]
yes
yes / no
T(mdo) [5.6.4]
5 s
Min.: 0 ms
Max.: 20 min
N x 5 s
Mute disable signal [5.6.7]
no
yes / no
Micro 400 interruption monitoring [5.6.8]
yes
yes
T(espe) [5.6.8]
2 s
Min.: 0 s
Max.: 10 s
N x 0.05 s (*)