Rockwell Automation FactoryTalk Historian SE ActiveView 3.2 User Guide User Manual

Page 55

Advertising
background image

3

For Developers: Administering FactoryTalk Historian ActiveView

47

Keyword

Section(s)

Description
the primary server becomes available, FactoryTalk

Historian ActiveView reverts to the primary server.
RequirePrimary specifies that FactoryTalk

Historian ActiveView only connects to the primary
server in the collective.

PB2TagResolution

Data Manager

Specifies how tags are resolved.
When set to 0, the default value, FactoryTalk

Historian ActiveView uses the saved Point ID over
the saved tag name. Use PB2TagResolution = 0,

when renaming Historian tags to resolve the tags
using the Point ID.
When set to 1, FactoryTalk Historian ActiveView
uses the saved tag name over the Point ID. use

PB2TagResolution = 1, when you want to use the
same tag but the tag has been moved from one

Historian Server (R&D) to another Historian
Server (Production)

EnableXPThemes

Startup

When set to 0, XP themes are not supported. This
setting allows viewing the VBA color palette from

the Properties window.

The values in the following example are not necessarily the default values.

[Startup]

ToolbarVisibility = 0

Show Value Attributes = 1

ConnectUsingAPI = 0

[Trend Definition]

MarkerWarning = 1

UpdateTimeRange = 604800

[XYPlot Definition]

UpdateTimeRange = 604800

Advertising