4-4

SB3000 Power Modules (Rittal)

4.3

Power Module Faults and Warnings

The PMI Processor continually runs diagnostics which check for errors that may affect
system operation. Warnings are errors which indicate that the SB3000 Synchronous
Rectifier is not operating in an optimum manner. Warnings will not shut down the
SB3000. Faults are severe errors which will shut down the SB3000. See tables 4.3
and 4.4.

Refer to the SB3000 Synchronous Rectifier Configuration and Programming
instruction manual (S-3034) for more information about the Fault and Warning
registers.

Table 4.1 – DC Bus and Output Terminal Tests

1

1. with the AC input lines disconnected

Meter Connections

+ -

Scale

Expected Test Results

DC Bus

- Bus (45)

+ Bus (47)

X10

Capacitor Effect (0 to 50 ohms)

+ Bus (47)

- Bus (45)

Capacitor Effect (0 to 200 ohms)

Bus

Capacitors

+

1249

X10

Capacitor Effect (0 to 500 ohms)

-

1249

601

+

X1

2 ohms

602

+

603

+

+

601

X10

Capacitor Effect (0 to 2k ohms)

+

602

+

603

Input

Terminals

181 (601)

182 (602)

X1000

4k to 6k ohms

181 (601)

183 (603)

182 (602)

183 (603

Table 4.2 – IGBT Tests

1

1. with the AC input lines disconnected

Meter

Connections

+ -

Scale

Expected Test

Results

(+/- 10%)

W Phase (lower) +

183

+1147

2k

/diode

0.300 ohms

V Phase (lower) +

182

+1147

2k

/diode

0.300 ohms

U Phase (lower) +

181

+ 1147

2k

/diode

0.300 ohms

W Phase (upper) -

1245 -

183

2k

/diode

0.300 ohms

V Phase (upper) -

1245 -

182

2k

/diode

0.300 ohms

U Phase (upper) -

1245 -

181

2k

/diode

0.300 ohms