Rockwell Automation SB3000 AC Power Modules User Manual

Page 60

Advertising
background image

A-2

SB3000 Power Modules (Rittal)

AC Input Power

Minimum AC Line Voltage: 208V nominal

Maximum AC Line Voltage: 460V nominal

Maximum AC Line Variation: +/- 10%

AC Line Frequency: 25, 50, and 60 Hz, +/- 2 Hz

Frequency Rate of Change: 1Hz/Second

Maximum AC Line Current: 534A, 972A, 1457A

Maximum Phase Imbalance: 5%

AC Control Power

AC Input Voltage: 115 VAC

AC Input Frequency: 50/60 Hz

DC Output Power

Minimum Output Voltage: 1.414 x VAC x 1.1 x 1.1

Maximum Output Voltage: 900V

Output Voltage Regulation: +/- 1%

Maximum DC Output Current: (1.70 x E

Line

x I

Line

x Power Factor) / VDC

Maximum Short Circuit Current: 100KA

Output Voltage Resolution: 0.5V

Output Voltage Regulation: Less than 5% for +/- 100% current step change

Voltage Regulator Response: 100 rad/sec.

VAR/Power Factor Correction: The user can select the maximum amount of
SB3000 VAR correction. The SB3000 Power Module will always give the
voltage regulator priority over the VAR function. If the output of the SB3000 Power
Module is less than its limit, it will attempt to produce VARs up to the limit set by the
user. Refer to Appendix C, section C.2.1.

SB3000 Power Module Current Ratings

1

SB3000 Part Number

Continuous

AC Input Current

(460VAC)

Continuous

DC Output Current

(800VDC)

5 Minute

AC Input and DC Output

Overload

2

804300-S

445A (rms)

445A DC

534A (rms)

804300-T

890A (rms)

890A DC

972A (rms)

804300-V

1335A (rms)

1335A DC

1457A (rms)

1. At 460 VAC Input/800 VDC Output/4 kHz Carrier Frequency. For use with SA3000/SA3100 Power Modules operating at a 2 kHz carrier

frequency.

2. With a 25% duty cycle