Double Pole Circuit Breaker Kit for Non-Regenerative MinPak Plus DC Drives

3

Step 3. Locate the standard, factory-installed single pole circuit breaker near the top of the drive. Remove its

two mounting screws and break away the metal tab on the top of the support bracket. Save the
Nomex™ shield for use with the double pole circuit breaker.

Step 4. Remove the two screws that fasten the terminal block and circuit breaker bracket to the chassis. Move

the bracket aside.

Step 5. Disconnect wire 181 from the existing breaker.

Step 6. Disconnect both wires 51 from the existing breaker.

Step 7. Disconnect the other end of wire 51 from 2TB and discard.

Step 8. Remove wires 182/52 and discard. One wire 182/52 connects 1TB and 2TB. The other connects 1TB

and the power cube.

Step 9. Connect the new jumper wire 182 to the new breaker on the side labeled “LINE” and to 1TB at L2.

Step 10. Connect wire 181 to the new breaker on the side labeled “LINE.”

Figure 1 – Wiring the Double Pole Circuit Breaker

Single Pole

Circuit Breaker

Double Pole

Circuit Breaker

51

52

2TB 1TB

181

51

181

L1

182

L2

“OFF” on
left side of
circuit breaker

X1

X2

Current

Transformer

Second Power
Cube (5 HP only)

Power
Cube

L1

L2

Power
Cube

L1

L2

Second Power
Cube (5 HP only)

Current

Transformer

X1

X2

181

182

51

52

LINE

LOAD

182/52

51

52

2TB 1TB

181

L1

182

L2

Discard

Discard

182/52

Discard

Disconnect

(steps 5 & 6)

(step 7)

(step 8)

(step 8)

Connect
(step 10)

Connect

(step 9)

Connect
(step 11)

Connect

(steps 12 & 13)

Connect

(step 15)

Connect
(step 14)

Connect

(step 9)