Replacing the Fan Capacitor on the Inverter Unit

1. If you are replacing a fan capacitor on a PowerFlex 700H drive inverter

unit, continue with step 2 on page

12

. For PowerFlex 700S drives, if you

are replacing the fan capacitor on the V phase of the inverter unit,
complete steps a.…c.
a. Disconnect the bus connection cable from connector J2 and the motor

feedback connection cable from connector J1 on the voltage feedback
board.

b. Disconnect the fiber-optic cables from connectors J4 and J5 on the

voltage feedback board.

c. Remove the four POZIDRIV screws that secure the voltage feedback

board assembly to the fan housing and remove the assembly. Tightening
torque for re-assembly is 1.35 N

m (12 lb

in).

IMPORTANT

Minimum inside bend radius for fiber-optic cable is 50 mm
(2 in.). Any bends with a shorter inside radius can
permanently damage the fiber-optic cable. Signal
attenuation increases with decreased inside bend radii.