Smart slot referencing, Location of smart slots – Rockwell Automation T8100 Trusted Controller Chassis User Manual

Page 12

Advertising
background image

Trusted

TM

TMR Controller Chassis T8100

Issue 12 Jul 12

PD-T8100

12

7. Smart Slot Referencing

For a Smart Slot configuration, the secondary slot is not required to be unique to each primary slot.
Instead, a single secondary slot can be shared among many primary slots. This technique provides
the highest density of modules to be fitted in a given physical space. Smart Slot between chassis can
be performed if the chassis are version 2 (or higher) as these have the connector fitted to enable
connection of a TC-006 that ensures the IMB 0V of each chassis is at the same potential.

7.1. Location of Smart slots

Design considerations should be given to the location of smart slots within the system. One option is to
allocate a spare slot on each chassis or per module type. Another option is to allocate one smart slot
per system panel; if this option is selected then the IMB 0V of each chassis needs connecting together
using a TC-006 cable. Each chassis (processor and expander) requires a TC-006 to connect to the
Molex socket on the back of each chassis. The crimps on the other end are taken to terminals that are
commoned together. This ensures that each isolated IMB 0v is at the same potential. Refer to PD-
TC000 for further information on TC-006.

Figure 6 Molex sockets on the rear of each processor and expander chassis

Molex socket for
IMB 0V connector
TC-006