Rockwell Automation T3488/T3488A ICS regent Monitored Guarded Output Modules User Manual

Page 18

Advertising
background image

Monitored Guarded Output Modules (T3481/81A, 84, and 88/88A)


1 8
(Issue 2)

Industrial Control Services

1) Set the Module Type:

Position the cursor on the module slot you wish to define.
Choose Set Module Type from the Edit Menu and select
the appropriate monitored guarded output module from
the list.

2) Edit the Module Definition:

Choose Edit Module Definition from the Edit Menu. A
dialog box will open where you can define the output point
definitions.

Figure 9. Monitored Guarded Output Module Definition.

3) Configure the module for single or dual mode.

With the cursor at the top of the list in the Module Definition
dialog shown in Figure 9, open the Monitored Guarded
Output Module Definition dialog by pressing Enter or double
clicking on the “(Module)” selection.

If the output module is to be used in dual mode (wired in
parallel with another similar module for fault tolerance), then
you must check the Dual Mode selection in the dialog box
shown in Figure 10. Also, you must enter the I/O Assembly
number (1-16) and I/O Slot number (1-10) of the redundant
module. This must be done for each of the two modules that
will operate in dual mode.

Advertising