24 Installing the XM-320 Position Module
Figures 2.9 and 2.10 illustrate the behavior of the NC and NO terminals when
the relay is wired for failsafe, alarm or nonalarm condition or non-failsafe,
alarm or nonalarm condition.
IMPORTANT
T
The NC/NO terminal descriptions (page 22) correspond
to a de-energized (unpowered) relay.
When the relay is configured for non-failsafe operation, the
relay is normally de-energized.
When the relay is configured for failsafe operation, the
relay is normally energized, and the behavior of the NC and
NO terminals is inverted.
Table 2.1 Relay Connections for XM-320
Configured for
Failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed Opened
COM
47
50
NO
48
49
Opened
Closed
COM 47
50
NC
46
51
Configured for
Non-failsafe Operation
Relay 1 Terminals
Nonalarm
Alarm
Wire Contacts
Contact 1
Contact 2
Closed
Opened
COM
47
50
NC
46
51
Opened
Closed
COM
47
50
NO
48
49