Triggered trend parameters – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual

Page 71

Advertising
background image

Publication GMSI10-UM005C-EN-P - May 2010

Configuration Parameters 63

Triggered Trend Parameters

The XM-320 can collect a triggered trend. A triggered trend is a time-based
trend that is collected when a relay on the XM-320 is activated, or the module
receives a trigger event.

Once the triggered trend is configured, the XM-320 continuously monitors the
trended measurements. When a trigger occurs, the XM-320 collects additional
data as specified by the Post Trigger parameter.

The XM-320 can only store one triggered trend. Unless the triggered trend is
latched, the trend data is overwritten with new data when the next trigger
occurs.

The triggered trend parameters define the trend data that is collected by the
module. Use these parameters to select the measurements included in the
trend records, the interval between trend records, and which relay triggers
(activates) the collection of the trend data.

IMPORTANT

The Triggered Trend parameters are not included in the
EDS file and cannot be edited using generic configuration
tools such as RSNetWorx for DeviceNet.

Triggered Trend Parameters

Parameter Name

Description

Values/Comments

Enable Triggered Trend
Measurements

Enable/disable the triggered trend measurements.
Select to configure the triggered trend
measurements.

Check to enable.
Clear to disable.

Select Measurements

Sets the measurements to be collected and stored in
the module.

More than one measurement can be
selected.

Number of Records

The maximum number of measurement sets that can
be collected in the trend buffer. The measurement
sets make up the trend data.

The Number of Records is
automatically calculated based upon
the number of Trended
Measurements
selected.

Latch Enable

Determines whether the trigger trend is latched or
unlatched.

Latched means that subsequent triggers are ignored
after the initial trigger. This prevents the trend data
from being overwritten with new data until the
trigger is manually reset (click Reset Trigger button).

Unlatched means that the trend data is overwritten
with new data every time a trigger occurs.

Check means latched
Clear means unlatched

Advertising