Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 79

Publication GMSI10-UM005C-EN-P - May 2010
Specifications 71
On-board Relay Rating
Failsafe
Latching
Time Delay
Voting Logic
Reset
Activation On
Maximum Voltage: 125V dc, 125V ac
Maximum Current: 3.5A*
Minimum Current: 0
Maximum Power: 60W, 62.5VA
*Max current is up to 40°C, then derates to 2A at
65°C.
Agency Rating:
120V ac @ 0.5A
110V dc @ 0.3A
30V dc @ 1.0A
Normally energized (failsafe), or
Normally de-energized (non-fail-safe)
Latching, or
Non-latching
0 to 25.5 seconds, adjustable in 100msec
increments
Single or paired "And" or "Or" logic applied
to any alarm
Local reset switch on top of module
Remote reset switch wired to terminal base
Digital reset command via serial or
DeviceNet interface
Alarm Status:
Normal
Alert
Danger
Disarm
Transducer fault
Module fault
Non-Volatile Configuration
A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.
*The configuration stored in non-volatile
memory can be deleted only by a module-reset
command sent via the serial interface, using
the Serial Configuration Utility, or via
DeviceNet from any compliant software
application.
Power
Module
Consumption
+21.6 to 26.4V dc
Maximum: 200mA
Typical: 165mA
XM-320 Technical Specifications
Product Feature
Specification