Pc serial port connection, Figure 2.24 non-contact sensor and lvdt wiring – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 44

Publication GMSI10-UM005C-EN-P - May 2010
36 Installing the XM-320 Position Module
Figure 2.24 Non-contact sensor and LVDT wiring
PC Serial Port Connection
The XM-320 includes a serial port connection that allows you to connect a PC
to it and configure the module’s parameters. There are two methods of
connecting an external device to the module’s serial port.
•
Terminal Base Unit - There are three terminals on the terminal base
unit you can use for the serial port connection. They are TxD, RxD, and
RTN (terminals 7, 8, and 9, respectively). If these three terminals are
wired to a DB-9 female connector, then a standard RS-232 serial cable
with 9-pin (DB-9) connectors can be used to connect the module to a
PC (no null modem is required).
0
16
22
6
Signal Ground
TYPICAL WIRING FO R NON-CONTACT SENSOR AND LINEAR VARIABLE
DIFFERENTIAL TRANSFORMER (LVDT) TO XM-320 POSITION MODULE
Power Ground
Input Signal
+24V DC
SIG
-24
COM
Shield
Channel 1 Input Signal
-24V DC
Signal Common
17
1
25
28
Signal Ground
Channel 2 Input Signal
+24V DC
Power Ground
Cable shield not
connected at this
end
Shield Floating
37
Shield
Isolated Sensor Driver
38