5 dc bus supply initial installation – Rockwell Automation SA500 DC Bus Supply User Manual
Page 19
 
Installation Guidelines
3-5
3.5
DC Bus Supply Initial Installation
The following procedure is intended to be only a guide to assist you in installing the 
DC bus supply. Refer to the wiring diagrams supplied with you system for more 
specific information.
Step 1. Mount the DC bus supply. DC bus supplies are designed to be mounted on a
flat surface using M5 or #10 screws. The holes in the top flange are key-hole 
shaped and the lower holes are U-shaped to facilitate mounting. The bus 
supply should be mounted in a location with good air flow and in close 
proximity to the SA500 AC Power Modules (3 mm (1/8 in) to 13 mm (1/2 in) 
spacing between units). See figure 3.1. Provide at least 85 mm (3.3 in) of 
clearance above and below the bus supply for ventilation.
Ambient air around the bus supply must be clean, dry, and free of flammable 
or combustible vapors, chemical fumes, oil vapor, steam, and excessive 
moisture and dirt.
The highest current AC Power Module should be placed closest to the bus 
supply. Note that the SA500 AC Power Modules (6 maximum) should be 
evenly distributed on each side of the bus supply. If two Power Modules are 
being used, one should be wired from the left of the bus supply and one 
should be wired from the right. If four Power Modules are being used, two 
should be wired from the left of the bus supply and two from the right. If an 
odd number of Power Modules is being used, they should be distributed as 
evenly as possible on each side of the bus supply. This method of Power 
Module placement minimizes wire length which reduces wire inductance. 
The continuous DC bus current for all SA500 AC Power Modules connected 
to the bus supply is limited to either 50A or 100A.